Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing: the ITR is held until it is attached.
ITR ACTIVITIES
1. Tag plate matches the register *YesNoN/A
2. Installed per hook-up drawing HU-82-014 *YesNoN/A
3. Calibrated range *
0 to 40 barg
4. Calibration check *
Test pointApplied (barg)Output (mA)Error (%)
0%0.004.000.0
50%20.0012.020.1
100%40.0019.98-0.1
5. Process connection leak-free *YesNoN/A
6. Remarks
Add a remark
Overview
Verify puts every inspection and test record on the device in the inspector's hand. Each answer is checked against the register and the datasheet before the signature goes in, so mistakes are fixed on site instead of found in the office days later.
Verify is part of Deskely Build, one of four suites across the life of a project. Every product reads from and writes to the same tag register, so each stage starts with clean data from the last.
Used by inspectors and technicians, qa/qc engineers, discipline supervisors and completions managers.
What Verify replaces.
Paper ITRs, scanned and retyped.
ITR_582-PT-820045_scan.pdf1 / 2
INSTRUMENT ITRFORM IN-04
Tag No582-PT-820045
Calibrated range0–25 bargDatasheet says 0–40
Reading at 50%12.0 mA
Calibration cert. attached–Not attached
Signed / dateJ.M. /Date missing
TodayFilled in by hand on site, scanned and retyped, with mistakes found days later.
Form No-IN-04 (Tag No: 582-PT-820045-A01)Activity Q(1-6)
✦ AI
Deskely AI check Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing: held until it is attached.
1. Tag plate matches the registerYes
2. Installed per hook-up drawing HU-82-014Yes
3. Calibrated range0 to 40 barg
4. Calibration checkWithin tolerance
5. Process connection leak-freeYes
HeldWaiting for the calibration certificate
With VerifyAnswered on site and checked against the register and datasheet before it is signed.
How Verify works
From check sheet to signature.
What happens to an ITR, from the tag on site to the signature.
01Open the ITR on site
The inspector opens the check sheet for the tag on a phone or tablet.
Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing: the ITR is held until it is attached.
ITR ACTIVITIES
1. Tag plate matches the register *YesNoN/A
2. Installed per hook-up drawing HU-82-014 *YesNoN/A
3. Calibrated range *
0 to 40 barg
4. Calibration check *
Test pointApplied (barg)Output (mA)Error (%)
0%0.004.000.0
50%20.0012.020.1
100%40.0019.98-0.1
5. Process connection leak-free *YesNoN/A
6. Remarks
Add a remark
02Answer and measure
Each question is answered on the spot, and readings are entered as they are taken.
Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing: the ITR is held until it is attached.
ITR ACTIVITIES
1. Tag plate matches the register *YesNoN/A
2. Installed per hook-up drawing HU-82-014 *YesNoN/A
3. Calibrated range *
0 to 40 barg
4. Calibration check *
Test pointApplied (barg)Output (mA)Error (%)
0%0.004.000.0
50%20.0012.020.1
100%40.0019.98-0.1
5. Process connection leak-free *YesNoN/A
6. Remarks
Add a remark
03Checked before signing
Each answer is checked against the register and the datasheet.
Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing: the ITR is held until it is attached.
ITR ACTIVITIES
1. Tag plate matches the register *YesNoN/A
2. Installed per hook-up drawing HU-82-014 *YesNoN/A
3. Calibrated range *
0 to 40 barg
4. Calibration check *
Test pointApplied (barg)Output (mA)Error (%)
0%0.004.000.0
50%20.0012.020.1
100%40.0019.98-0.1
5. Process connection leak-free *YesNoN/A
6. Remarks
Add a remark
04Sign when it is right
Anything missing holds the ITR. Once it is fixed, the inspector signs on site.
Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing: the ITR is held until it is attached.
ITR ACTIVITIES
1. Tag plate matches the register *YesNoN/A
2. Installed per hook-up drawing HU-82-014 *YesNoN/A
Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing: the ITR is held until it is attached.
ITR ACTIVITIES
1. Tag plate matches the register *YesNoN/A
2. Installed per hook-up drawing HU-82-014 *YesNoN/A
Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing: the ITR is held until it is attached.
ITR ACTIVITIES
1. Tag plate matches the register *YesNoN/A
2. Installed per hook-up drawing HU-82-014 *YesNoN/A
Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing: the ITR is held until it is attached.
ITR ACTIVITIES
1. Tag plate matches the register *YesNoN/A
2. Installed per hook-up drawing HU-82-014 *YesNoN/A
Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing: the ITR is held until it is attached.
ITR ACTIVITIES
1. Tag plate matches the register *YesNoN/A
2. Installed per hook-up drawing HU-82-014 *YesNoN/A
3. Calibrated range *
0 to 40 barg
4. Calibration check *
Test pointApplied (barg)Output (mA)Error (%)
0%0.004.000.0
50%20.0012.020.1
100%40.0019.98-0.1
5. Process connection leak-free *YesNoN/A
6. Remarks
Add a remark
Verify does the checking. Inspectors make the calls.
Tag found in the register · Range matches the datasheet · Readings within tolerance · Calibration certificate missing:2 the ITR is held until it is attached.
ITR ACTIVITIES
1. Tag plate matches the register *YesNoN/A
2. Installed per hook-up drawing HU-82-014 *YesNoN/A
3. Calibrated range *
0 to 40 barg
4. Calibration check *
Test pointApplied (barg)Output (mA)Error (%)
0%0.004.000.0
50%20.0012.020.1
100%40.0019.98-0.1
5. Process connection leak-free *YesNoN/A
6. Remarks
Add a remark
1Checked by Verify
Each answer against the register and the datasheet: tag, range and readings.
2Held for review
A missing certificate or a reading out of tolerance holds the ITR, with the reason.