GUIDEResources / GuidesUpdated 29 Oct 2026 · 5 min read

Hazardous area classification: zones, divisions, gas groups and Ex markings

Deskely Completions team Singapore

Hazardous area classification divides a plant into zones by how likely an explosive atmosphere is to be present, so that the electrical and mechanical equipment in each zone can be chosen so it cannot ignite it. It decides what can be installed where, and every item installed there has to be inspected against it.

This guide covers the IEC zone system and the North American class and division system, gas groups and temperature classes, the Ex protection types, how to read an Ex marking, and the inspection records a project keeps.

Key takeaways
  • Zone 0, 1 and 2 (gas) and Zone 20, 21 and 22 (dust) rank how often an explosive atmosphere is present.
  • North America also uses Class I, II, III with Division 1 and 2, now alongside zones.
  • Equipment must suit the zone (EPL), the gas group (IIA, IIB, IIC) and the temperature class (T1 to T6).
  • Every Ex item is inspected before start-up and recorded against its tag, in an Ex register.

Zones for gas and dust

The IEC system, used internationally and in Europe under ATEX, classifies areas by how often an explosive atmosphere is present. Gas zones follow IEC 60079-10-1 and dust zones IEC 60079-10-2.

ZoneExplosive atmosphere is presentTypical examples
Zone 0Continuously, for long periods or frequentlyInside tanks and vessels above the liquid
Zone 1Likely to occur occasionally in normal operationAround vents, pump seals and sample points
Zone 2Not likely in normal operation, and only for a short time if it doesAround flanges and valves in process areas
Zone 20Combustible dust cloud continuously, for long periods or frequentlyInside silos, hoppers and mills
Zone 21Dust cloud likely occasionally in normal operationAround filling and emptying points
Zone 22Dust cloud not likely, and only briefly if it doesAreas near dust-handling equipment

Areas outside these zones are non-hazardous (safe areas). The extent of each zone around a source of release is set by the area classification study and drawn on the hazardous area classification drawings.

Classes and divisions (North America)

In the US and Canada the traditional system, in NEC Article 500 and the Canadian Electrical Code, uses classes for the type of material and divisions for how likely it is to be present. NEC Articles 505 and 506 also allow the zone system.

Class and divisionMeaningClosest zones
Class I, Division 1Flammable gas or vapour present in normal operationZone 0 and Zone 1
Class I, Division 2Flammable gas or vapour present only in abnormal conditionsZone 2
Class IICombustible dust, Division 1 or 2Zones 20, 21 and 22
Class IIIIgnitable fibres and flyingsDust zones for fibres

Gas groups

Gases are grouped by how easily their flames pass through gaps and how little energy ignites them. Equipment rated for a more demanding group can be used in a less demanding one: IIC equipment is suitable for IIB and IIA.

IEC groupTypical gasNEC group
IIAPropaneGroup D
IIBEthyleneGroup C
IICHydrogenGroup B
IICAcetyleneGroup A
IMethane in underground mines (firedamp)Mining
IIIA, IIIB, IIICCombustible flyings, non-conductive dust, conductive dustClass II and III

Temperature classes

The temperature class gives the highest surface temperature the equipment can reach. It must stay below the auto-ignition temperature of the gas in the area.

Temperature classMaximum surface temperature
T1450 °C
T2300 °C
T3200 °C
T4135 °C
T5100 °C
T685 °C

A T4 item can go anywhere a T3, T2 or T1 item can. Hydrogen, for example, needs only T1, while carbon disulphide needs T6.

Equipment protection levels and ATEX categories

ZoneEquipment protection level (EPL)ATEX category
Zone 0Ga1G
Zone 1Gb (or Ga)2G
Zone 2Gc (or Gb, Ga)3G
Zone 20Da1D
Zone 21Db (or Da)2D
Zone 22Dc (or Db, Da)3D

In Europe, equipment for hazardous areas is placed on the market under the ATEX equipment directive 2014/34/EU, and workplaces are classified under directive 1999/92/EC. Internationally, the IECEx scheme certifies equipment to the IEC 60079 series.

Ex protection types

CodeProtection typeHow it works
Ex dFlameproof enclosureContains an internal explosion and stops it spreading outside
Ex eIncreased safetyPrevents arcs, sparks and hot surfaces by design
Ex i (ia, ib, ic)Intrinsic safetyLimits the energy in the circuit below what can ignite the gas
Ex pPressurised enclosureKeeps the gas out with clean air or inert gas at overpressure
Ex mEncapsulationSeals the ignition source in compound
Ex oLiquid immersionImmerses the parts in a protective liquid
Ex qPowder fillingFills the enclosure with powder, such as quartz sand
Ex tProtection by enclosure (dust)Keeps dust out and limits surface temperature

How to read an Ex marking

A typical IECEx or ATEX marking reads Ex db IIB T4 Gb:

  • Ex: equipment for explosive atmospheres.
  • db: protection type, here flameproof enclosure at level b.
  • IIB: gas group, suitable for IIB and IIA gases.
  • T4: temperature class, surface temperature not above 135 °C.
  • Gb: equipment protection level, suitable for Zone 1 and Zone 2.

ATEX equipment also carries the Ex hexagon with the group and category, such as II 2G, and the certificate number. The installation must match all of these to the zone, gas group and temperature class on the area classification drawing.

Ex inspection and the Ex register

Installed Ex equipment is inspected before it is put into service and then periodically, following IEC 60079-17. The initial inspection is usually a detailed inspection of every item: the right certificate and marking for the location, cable glands and entries, enclosure condition, earthing and, for intrinsically safe circuits, the loop documentation.

Each inspection is recorded against the tag in an Ex register: the list of every item of equipment in a hazardous area, with its location, zone, marking, certificate and inspection history. Faults become punch items, and A items stop the system from being energised. See the ITR guide and the punch list template.

In Deskely, Ex inspections are set up as your own inspection record templates and filled in against each tag like any other ITR, so open Ex findings show on the subsystem and the certificates they hold back.

The Deskely products for this

Frequently asked questions

What is the difference between Zone 1 and Zone 2?

In Zone 1 an explosive gas atmosphere is likely to occur occasionally in normal operation. In Zone 2 it is not likely in normal operation, and if it occurs it lasts only a short time.

What is Class I Division 1?

The North American classification for areas where flammable gas or vapour is present in normal operation. It corresponds roughly to Zone 0 and Zone 1.

What does T4 mean on Ex equipment?

Temperature class T4: the maximum surface temperature of the equipment does not exceed 135 °C.

Which gas group is hydrogen?

IIC in the IEC system, Group B in the NEC system. Acetylene is also IIC (Group A).

What does Ex d mean?

Flameproof enclosure: the enclosure can contain an explosion inside it and stop it from igniting the atmosphere outside.

What is an Ex register?

The list of all equipment installed in hazardous areas, with location, zone, Ex marking, certificate and inspection history for each item.