ANSI device numbers name the functions of protective relays and switchgear on single line diagrams, relay settings and schematics: 52 is a circuit breaker, 51 an overcurrent relay, 87 a differential relay. They are defined in IEEE C37.2. The list below gives the common numbers with the IEC 60617 qualifier and the IEC 61850 logical node used for the same function.

Standard
IEEE C37.2-2022, IEEE Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations
Content
95 device function numbers and 22 acronyms, with prefixes, suffixes and contact designations
Newer acronyms
Cover functions such as arc flash detection, phasor measurement units, digital fault recorders and remedial action schemes

ANSI device number list

No.FunctionIEC 60617IEC 61850
1Master element
2Time-delay starting or closing relay
3Checking or interlocking relay
12Overspeed device
14Underspeed device
21Distance relayZ<PDIS
24Volts per hertz relayU/f>
25Synchronizing or synchronism-check deviceRSYN
26Apparatus thermal device
27Undervoltage relayU<PTUV
30Annunciator relay
32Directional power relay (reverse power)PDOP, PDUP
37Undercurrent or underpower relayI<PTUC
38Bearing protective device
40Field (loss of excitation) relay
46Reverse-phase or phase-balance current relay (negative sequence)I2>
47Phase-sequence or phase-balance voltage relayU2>
48Incomplete sequence relay
49Machine or transformer thermal relayθ>PTTR
50Instantaneous overcurrent relayI>>PIOC
51AC inverse time overcurrent relayI>PTOC
52AC circuit breakerXCBR
55Power factor relay
57Short-circuiting or grounding device
59Overvoltage relayU>PTOV
60Voltage or current balance relay
62Time-delay stopping or opening relay
63Pressure switch (sudden pressure relay on transformers)
64Ground detector relay
66Notching or jogging device (starts per hour)
67AC directional overcurrent relayI> with direction arrow
68Blocking or out-of-step relay
69Permissive control device
71Liquid level switch
72DC circuit breaker
74Alarm relay
76DC overcurrent relay
78Phase-angle measuring or out-of-step protective relay
79Reclosing relayRREC
81Frequency relayf<, f>PTUF, PTOF
83Automatic selective control or transfer relay
85Pilot communications, carrier or pilot-wire relay
86Lockout relay
87Differential protective relayId>PDIF
89Line switch (disconnect)XSWI
90Regulating device
94Tripping or trip-free relay

The IEC columns give the qualifier and logical node most often used for the same function. Not every ANSI number has a direct IEC equivalent.

Suffixes

Letters after the number narrow the function down. They show what is measured or protected:

SuffixMeaning
NNeutral, for example 51N, residual overcurrent
GGround, measured with a ground CT, as in 51G, or generator, as in 87G
TTransformer, as in 87T
BBus, as in 87B
LLine, as in 87L
MMotor, as in 87M
VVoltage controlled or restrained, as in 51V
BFBreaker failure, as in 50BF

Combinations you will see on one-lines

  • 50/51: instantaneous and time overcurrent in one relay, the most common feeder protection.
  • 50N/51N or 50G/51G: earth fault overcurrent, residual or from a ground CT.
  • 87T, 87G, 87B, 87M: differential protection of a transformer, generator, busbar or motor.
  • 27/59: under and overvoltage, often with 81O/81U for over and under frequency.
  • 86: the lockout relay that trips the breakers and must be reset by hand.
  • 52a and 52b: the auxiliary contacts of a breaker. 52a is closed when the breaker is closed, 52b is the opposite.

Frequently asked questions

What are ANSI device numbers?

Numbers defined in IEEE C37.2 that identify the function of a device in electrical power systems, such as 52 for an AC circuit breaker or 87 for a differential relay. They are used on single line diagrams, schematics and relay settings.

What is 50/51 protection?

50 is instantaneous overcurrent and 51 is AC inverse time overcurrent. A 50/51 relay provides both, and is the standard protection on feeders.

What is device 86?

A lockout relay. It trips the breakers and holds them open until it is reset by hand, so equipment is not re-energised onto a fault.

What is device 87?

A differential protective relay. It compares the current going into and out of a zone, such as a transformer (87T) or busbar (87B), and trips if they differ.

What is the IEC equivalent of ANSI 51?

An overcurrent relay marked I> (IEC 60617), PTOC in IEC 61850.

Every breaker and transformer on your one-line, tested and energised.Deskely holds the tag register, test records and punch items for every electrical tag on your project, through to handover.
  • In production since 2014
  • Thousands of daily users
  • On MODEC FPSO projects since 2016

The symbols on this page were drawn by Deskely and are free to use. Standards are revised and every project issues its own legend sheets, which take precedence.

Autonomous engineering runs on Deskely.

Talk to sales