GUIDEResources / GuidesUpdated 29 Oct 2026 · 6 min read

Insulation resistance test (megger test): procedure, minimum values and PI calculator

Deskely Completions team Singapore

An insulation resistance test applies a DC voltage between a conductor and earth, or between conductors, and measures the resistance of the insulation in megohms. It is the most common electrical test on a project: on every cable after it is pulled, and on every motor, transformer and switchboard before it is energised.

Electricians call it a megger test, after the Megger brand of tester. This guide covers the test voltages, the minimum values in IEEE 43 and IEC 60364-6, the polarization index, temperature correction, and how the result is recorded. A calculator does the arithmetic.

Key takeaways
  • Pick the test voltage from the rated voltage of the equipment, and disconnect anything electronic first.
  • Machines: IEEE 43 recommends at least 100 MΩ for modern form-wound windings and 5 MΩ for random-wound ones, corrected to 40 °C.
  • Installations: IEC 60364-6 asks for at least 1 MΩ at 500 V on circuits up to 500 V.
  • The polarization index (10 minute reading over 1 minute reading) should be at least 2.0 for class B, F and H insulation.

What an insulation resistance test is

The tester applies a steady DC voltage, typically 500 V to 5 kV, and measures the small current that leaks through and across the insulation. Resistance is voltage divided by current, so good insulation reads hundreds or thousands of megohms; damp, dirty or damaged insulation reads low.

The test is non-destructive at the right voltage, quick and repeatable, which is why it is the first electrical check on almost every item. It does not prove the insulation will withstand a high voltage: that is the job of a withstand (hipot) test.

When it is done

  • After cable installation: every power and control cable, conductor to conductor and conductor to earth, usually on a construction (A) ITR.
  • Before energising: motors, transformers, switchgear and busbars, on pre-commissioning (B) ITRs.
  • Before a motor solo run, and again after long storage or if the equipment has been wet.
  • In maintenance, where the trend over the years matters more than a single value.

See the ITR guide for how these records fit into completion and commissioning.

Test voltages

For rotating machines, IEEE 43 recommends the DC test voltage by the rated voltage of the winding:

Winding rated voltageDC test voltage
Below 1,000 V500 V
1,000 to 2,500 V500 to 1,000 V
2,501 to 5,000 V1,000 to 2,500 V
5,001 to 12,000 V2,500 to 5,000 V
Above 12,000 V5,000 to 10,000 V

For low voltage installations, IEC 60364-6 (BS 7671 in the UK) gives the test voltage and the minimum together:

CircuitDC test voltageMinimum insulation resistance
SELV and PELV250 V0.5 MΩ
Up to and including 500 V500 V1.0 MΩ
Above 500 V1,000 V1.0 MΩ

Project specifications and manufacturers often ask for higher values than these minimums. Use the figure in your test procedure.

How to do the test

  1. 01
    Isolate and prove dead

    Work under the permit and isolation procedure. Lock off, test for dead, and earth the circuit until the tester is connected.

  2. 02
    Disconnect what the test could damage

    Drives, soft starters, electronic relays, surge arresters, capacitors and instruments. Open neutral links where needed.

  3. 03
    Connect the tester

    Between each conductor and earth, and between conductors where the procedure calls for it. On a motor, test the winding to earth with the other phases connected to earth, or all three phases together.

  4. 04
    Apply the voltage and read

    Read at 1 minute for a spot reading. For a polarization index, keep the voltage on and read again at 10 minutes.

  5. 05
    Record the conditions

    Winding or cable temperature, humidity, test voltage, readings and the tester serial number and calibration date.

  6. 06
    Discharge

    Earth the conductor after the test, for several times as long as the voltage was applied. Long cables and large windings hold a dangerous charge.

Minimum values for machines (IEEE 43)

IEEE 43 gives a recommended minimum for the 1 minute reading, corrected to 40 °C:

WindingRecommended minimum at 40 °C
Most AC and DC windings built after about 1970 (form-wound coils)100 MΩ
Most machines with random-wound stator coils, and form-wound coils rated below 1 kV5 MΩ
Most windings built before about 1970, all field windings, and othersRated kV + 1 MΩ

A reading above the minimum does not prove a winding is good, and a single low reading does not prove it is bad. The trend and the polarization index tell you more.

Polarization index and dielectric absorption

When DC is applied, the current through good insulation keeps falling for several minutes as the insulation polarises, so the resistance keeps rising. Damp or contaminated insulation leaks steadily and the reading barely changes.

  • Polarization index (PI) = reading at 10 minutes / reading at 1 minute. IEEE 43 recommends at least 2.0 for class B, F and H insulation, and 1.5 for class A.
  • Dielectric absorption ratio (DAR) = reading at 60 seconds / reading at 30 seconds. A quicker check, often used on smaller equipment.
  • If the 1 minute reading is above 5,000 MΩ (5 GΩ), the PI may not be meaningful and IEEE 43 does not require it.

Because PI and DAR are ratios taken at the same temperature, they need no temperature correction.

Temperature correction

Insulation resistance falls as temperature rises, so readings are corrected to a common base, 40 °C for machines in IEEE 43. A common rule of thumb is that resistance halves for every 10 °C rise:

R at 40 °C = R measured x 0.5 ^ ((40 - T) / 10), where T is the winding temperature in °C. A reading of 800 MΩ at 20 °C corrects to 200 MΩ at 40 °C.

The rule of thumb is an approximation. For trending, take readings at similar temperatures or use the correction curve from the manufacturer.

Insulation resistance calculator

Enter the rated voltage, the winding type, the readings and the temperature. The calculator gives the IEEE 43 test voltage, corrects the reading to 40 °C, compares it with the recommended minimum and works out the polarization index.

Insulation resistance calculator
Test voltage (IEEE 43)
2,500 to 5,000 V DC
Reading corrected to 40 °C
300.5 MΩ
Recommended minimum
100 MΩ · above
Polarization index
2.82 · minimum 2.0

A guide based on the IEEE 43 recommended values and the rule of thumb that resistance halves for every 10 °C rise. Your test procedure and the manufacturer’s values take precedence.

Record readings against the tag, with low values flagged before sign-off: Deskely Verify

Recording the result

An insulation resistance test is only useful if it can be found and trusted later. The record, usually an ITR, should hold:

  • The tag of the cable, motor or switchboard, and its system and subsystem.
  • The test voltage, the readings for each phase to earth and phase to phase, and the PI where taken.
  • The temperature and humidity at the time of the test.
  • The tester, its serial number and calibration due date.
  • The acceptance value from the procedure, the result, and the signatures.

In Deskely, these readings are entered on the tablet against the tag, and Deskely Verify flags values outside range or tolerance before the record is signed, so a low reading becomes a punch item on site rather than a surprise at energisation.

The Deskely products for this

Frequently asked questions

What is a megger test?

An insulation resistance test. Megger is the brand of the first portable insulation testers, and the name stuck for the test itself.

What is a good insulation resistance value?

It depends on the equipment. IEEE 43 recommends at least 100 MΩ at 40 °C for modern form-wound machine windings and 5 MΩ for random-wound ones. IEC 60364-6 asks for at least 1 MΩ on low voltage installation circuits up to 500 V. Many specifications ask for more.

What voltage should I use for an insulation resistance test?

For machines, IEEE 43 recommends 500 V DC below 1 kV, rising to 5 to 10 kV DC above 12 kV. For low voltage installations, IEC 60364-6 uses 500 V DC for circuits up to 500 V. Use the voltage in your test procedure.

What is the polarization index?

The 10 minute insulation resistance reading divided by the 1 minute reading. A PI of 2.0 or more is recommended for class B, F and H insulation.

Why are readings corrected to 40 °C?

Insulation resistance changes strongly with temperature, so readings are corrected to a common base to compare them with the minimum and with earlier tests.

Can I megger a cable connected to a VFD?

No. Disconnect drives, soft starters and other electronics before the test, or the test voltage can damage them.

What is the difference between an insulation resistance test and a hipot test?

An insulation resistance test measures resistance at a moderate DC voltage and is non-destructive. A hipot (withstand) test applies a higher voltage to prove the insulation can withstand it.

Catch the low reading on site, not at energisation.Deskely Verify records insulation readings against the tag on a tablet and flags values outside range or tolerance before the record is signed.