TEMPLATEResources / TemplatesUpdated 8 Nov 2026 · 4 min read

Solar PV string test report: free IEC 62446-1 test sheet (Excel and PDF)

Deskely Completions team Singapore

A solar PV string test report records the category 1 tests of IEC 62446-1 on each string of a PV array: open circuit voltage against the expected value, string current, polarity and insulation resistance of the positive and negative conductors to earth, together with the irradiance, temperature and instruments used.

This page gives you a free string test report in Excel and PDF: site, inverter and combiner box header, instruments with calibration dates, module data, an automatic test voltage and minimum insulation resistance from the system voltage, and a string table that works out the expected Voc and Isc and flags deviations, low insulation and reversed polarity.

Key takeaways
  • Expected Voc = modules in series × Voc at STC, corrected for module temperature.
  • Strings of the same design should agree closely; a common acceptance band is ±5 % of expected Voc.
  • IEC 62446-1 insulation test: 1 MΩ minimum at 500 V or 1000 V test voltage for systems above 120 V.
  • Record irradiance and temperature with every test, or the readings cannot be compared.

The category 1 tests on a string

IEC 62446-1 (Photovoltaic systems, requirements for testing, documentation and maintenance, part 1: grid connected systems) sets the minimum tests for every system as category 1. Those made string by string are:

TestWhat it confirmsTypical fault found
PolarityPositive and negative connected the right way, before isolators are closedA reversed string, which can damage the inverter
Open circuit voltage (Voc)The right number of modules, all connected, in the stringA missing, bypassed or reversed module, a wrong string length
String current (Isc or operating)Current in line with irradiance and with the other stringsShading, damaged modules, poor connections
Insulation resistanceNo leakage path from the DC conductors to earthDamaged cable insulation, water in a connector

Category 1 also covers continuity of protective earthing and bonding, the combiner box test and functional tests; the template has a short check list for those per combiner box. Category 2 adds I-V curve tracing and infrared thermography. See the solar commissioning guide for the full sequence.

Expected Voc and the 5 % check

Expected Voc = modules in series × Voc at STC × (1 + temperature coefficient of Voc / 100 × (module temperature − 25 °C)). Voc falls as the module warms, so a cold morning reads high and a hot afternoon low.

ExampleValue
Modules in series24
Voc at STC (datasheet)49.5 V
Temperature coefficient of Voc−0.26 %/°C
Module temperature45 °C
Expected string Voc24 × 49.5 × (1 − 0.0026 × 20) = 1126 V
Measured 1131 VDeviation +0.4 %: pass

A common acceptance band is ±5 % of the expected value. Note that one missing or bypassed module in a 24-module string lowers Voc by about 4 %, inside that band, so also compare each string with its neighbours measured at the same time: strings of the same design should read within a few volts of each other.

Insulation resistance: test voltage and minimum

IEC 62446-1 sets the test voltage and the minimum insulation resistance by the system voltage, taken as Voc at STC × 1.25:

System voltage (Voc STC × 1.25)Test voltageMinimum insulation resistance
Below 120 V250 V0.5 MΩ
120 V to 500 V500 V1 MΩ
Above 500 V1000 V1 MΩ

The template works the system voltage out from the longest string and the module data, and picks the test voltage and minimum from this table. If your specification asks for a higher minimum, enter it and the results use that instead. Test with the array isolated from the inverter, test positive to earth and negative to earth, and never break a DC connector under load. Readings of a few MΩ on a large array are worth investigating even when they pass. See the insulation resistance test guide.

What is in the template

PV string test report template with site, inverter, combiner box, irradiance and temperature fields, an instruments table with calibration dates, module data, and an insulation test voltage and minimum resistance calculator
The free PV string test report, page one. The string table follows.
SheetFields
String test (header)Site, report number, revision, date, inverter, combiner box, block, tested by, irradiance in plane (W/m²), module temperature, ambient temperature, sky conditions
String test (instruments and modules)PV tester, insulation tester and irradiance meter with make, serial, calibration due and certificate; up to three module types with Voc and Isc at STC and the Voc temperature coefficient
String test (limits)System voltage, test voltage and minimum insulation resistance worked out to IEC 62446-1, an optional project minimum, and the Voc tolerance (5 % by default); category 1 checks for the combiner box
String test (strings)String ID, module type, modules in series, expected Voc, measured Voc, Voc deviation, expected Isc, measured Isc, Isc deviation, polarity, insulation + and − to earth, insulation result, overall result, remarks; two worked example rows and live counts of passes, fails, Voc outside tolerance, low insulation and reversed polarity

Where string tests fit

String tests come after the visual inspection of modules, mounting, cabling and connectors, and before the inverters are commissioned. On a utility-scale plant they run block by block, then the collection system and plant substation follow, much like any substation commissioning. The megger test report covers insulation tests on the AC side.

String tests in Deskely

Deskely records string, combiner and inverter tests on a tablet against each tag and checks readings against expected values as they are entered.

The Deskely products for this

Frequently asked questions

How do you calculate the expected Voc of a solar string?

Multiply the number of modules in series by the module Voc at STC, then correct for temperature: multiply by 1 + the Voc temperature coefficient (in %/°C, divided by 100) × (module temperature − 25 °C).

What is an acceptable Voc deviation for a PV string?

A common acceptance band is ±5 % of the expected value. Compare strings of the same design with each other as well, since one missing module can sit inside 5 %.

What is the minimum insulation resistance for a PV array?

Under IEC 62446-1, 1 MΩ for systems above 120 V (tested at 500 V up to 500 V system voltage, 1000 V above), and 0.5 MΩ at 250 V for systems below 120 V.

What test voltage is used for PV insulation resistance?

It depends on the system voltage, Voc at STC × 1.25: 250 V below 120 V, 500 V from 120 to 500 V, and 1000 V above 500 V.

Why record irradiance during string tests?

String current is proportional to irradiance, so a current reading means little without it. Test under steady irradiance and record it with every set of readings.

Thousands of strings, typed into spreadsheets twice?Deskely records string, combiner and inverter tests on a tablet against each tag and checks readings against expected values as they are entered.
  • In production since 2014
  • Thousands of daily users
  • On MODEC FPSO projects since 2016

Autonomous engineering runs on Deskely.

Talk to sales