Current transformer (CT) symbol

Also called CT

A current transformer steps the line current down to a small secondary current (1 A or 5 A) for meters and protective relays. Its ratio, such as 600/5, is written next to it.

ANSI / IEEE
IEC 60617 · S00850

What the current transformer (CT) symbol means

A current transformer steps the line current down to a small secondary current (1 A or 5 A) for meters and protective relays. Its ratio, such as 600/5, is written next to it.

ANSI and IEC symbols

ANSI / IEEE 315

A small loop beside the conductor, with a polarity dot and the ratio written next to it.

ANSI SVG
IEC 60617S00850

Current transformer, general symbol (form 1). A circle threaded on the conductor. The coil form is S00851.

IEC SVG

Where you see it

On every breaker that has protection or metering, often several CTs per breaker for different relays.

What is written next to it

On a one-line, the current transformer (CT) carries its tag and its ratings: ratio (for example 600/5 A), accuracy class (5P20 for protection, 0.5 for metering) and burden in VA.

What gets checked at commissioning

Before the current transformer (CT) is energised, the test records usually cover: ratio, polarity, insulation resistance, winding resistance and the excitation (knee point) curve. Each check is recorded against the tag, so the system can be handed over with its evidence. See commissioning software.

ANSI device numbers

Protective functions you will often find with a current transformer (CT):

  • 50/51 overcurrent
  • 87 differential

See the full list of ANSI device numbers with their IEC equivalents.

Frequently asked questions

What does the current transformer (CT) symbol look like?

On ANSI drawings: A small loop beside the conductor, with a polarity dot and the ratio written next to it. In IEC 60617: A circle threaded on the conductor. The coil form is S00851.

Is the current transformer (CT) symbol the same in IEC and ANSI?

No. A circle threaded on the conductor. The coil form is S00851. The IEC 60617 number is S00850.

Where is a current transformer (CT) used?

On every breaker that has protection or metering, often several CTs per breaker for different relays.

Which ANSI device numbers go with a current transformer (CT)?

50/51 overcurrent, 87 differential.